PANASONİC KLİMA ARIZA KODLARI
Klima Arıza KodlarıPanasonic Klima Arıza Kodları..
Diagnosis display = H00
Abnormality / Protection control = No abnormality detected
Abnormality Judgement =
Emergency operation = Normal operation
Primary location to verify =
Diagnosis display = H11
Abnormality / Protection control = Indoor / Outdoor abnormal communication
Abnormality Judgement = > 1 min after starting operation
Emergency operation = Indoor fan operation only
Primary location to verify = • Internal / external cable connections • Indoor / Outdoor PCB
Diagnosis display = H14
Abnormality / Protection control = Indoor intake air temperature sensor abnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation =
Primary location to verify = • Intake air temperature sensor (detective or disconnected)
Diagnosis display = H15
Abnormality / Protection control = Outdoor compressor temperature sensor abnormality
Abnormality Judgement = Continue for 5 sec
Emergency operation =
Primary location to verify = Compressor temperature sensor (detective or disconnected)
Diagnosis display = H16
Abnormality / Protection control = Outdoor Current Transformer open circuit
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Outdoor PCB • IPM (Power transistor) module
Diagnosis display = H19
Abnormality / Protection control = Indoor fan motor mechanism locked
Abnormality Judgement = 7 times occurance continuously
Emergency operation =
Primary location to verify = • Indoor PCB • Fan motor
Diagnosis display = H23
Abnormality / Protection control = Indoor heat exchanger temperature sensor abnormality
Abnormality Judgement =
Emergency operation = O (Cooling only}
Primary location to verify = • Heat exchanger temperature sensor (detective or disconnected)
Diagnosis display = H24
Abnormality / Protection control = Indoor heat exchanger temperature sensor 2 abnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation =
Primary location to verify = • Heat exchanger temperature sensor (detective or disconnected)
Diagnosis display = H27
Abnormality / Protection control = Outdoor intake air temperature sensor abnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation = O
Primary location to verify = • Outdoor temperature sensor (detective or disconnected)
Diagnosis display = H28
Abnormality / Protection control = Outdoor heat exchanger temperature sensor abnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation = O
Primary location to verify = • Outdoor heat exchanger temperature sensor (detective or disconnected)
Diagnosis display = H30
Abnormality / Protection control = Outdoor discharge air temperature sensor abnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation =
Primary location to verify = • Outdoor temperature sensor (detective or disconnected)
Diagnosis display = H33
Abnormality / Protection control = Indoor / Outdoor wrong connection
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Indoor / Outdoor supply voltage
Diagnosis display = H38
Abnormality / Protection control = Indoor / Outdoor mismatch (brand code)
Abnormality Judgement =
Emergency operation =
Primary location to verify =
Diagnosis display = H50
Abnormality / Protection control = Ventilation motor abnormality
Abnormality Judgement = 7 times occurance continuously
Emergency operation =
Primary location to verify = • Indoor PCB • Ventilation motor
Diagnosis display = H51
Abnormality / Protection control = Nozzle lock abnormality
Abnormality Judgement = 2 times occurance continuously
Emergency operation =
Primary location to verify = •Nozzle
Diagnosis display = H52
Abnormality / Protection control = Limit switch abnormality
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Indoor PCB
Diagnosis display = H97
Abnormality / Protection control = Outdoor fan motor mechanism locked
Abnormality Judgement = 2 times occurance within 30 minutes
Emergency operation =
Primary location to verify = • Indoor PCB • Fan motor
Diagnosis display = H98
Abnormality / Protection control = Indoor high pressure protection
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Air filter dirty • Air circulation short circuit
Diagnosis display = H99
Abnormality / Protection control = Indoor heat exchanger anti-freezing protection
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Insufficient refrigerant • Air filter dirty
Diagnosis display = F11
Abnormality / Protection control = Cooling / Heating cycle changeover abnormality
Abnormality Judgement = 4 times occurance within 30 minutes
Emergency operation =
Primary location to verify = •4-way valve • V-coil
Diagnosis display = F90
Abnormality / Protection control = PFC control
Abnormality Judgement = 4 times occurance within 10 minutes
Emergency operation =
Primary location to verify = • Voltage at PFC
Diagnosis display = F91
Abnormality / Protection control = Refrigerantion cycle abnormality
Abnormality Judgement = 2 times occurance within 20 minutes
Emergency operation =
Primary location to verify = • No refrigerant (3-way valve is closed)
Diagnosis display = F93
Abnormality / Protection control = Compressor rotation failure
Abnormality Judgement = 4 times occurance within 20 minutes
Emergency operation =
Primary location to verify = •Compressor
Diagnosis display = F95
Abnormality / Protection control = Cool high pressure protection
Abnormality Judgement = 4 times occurance within 20 minutes
Emergency operation =
Primary location to verify = • Outdoor refrigerant circuit
Diagnosis display = F96
Abnormality / Protection control = IPM (power transistor) overheating protection
Abnormality Judgement = 4 times occurance within 30 minutes
Emergency operation =
Primary location to verify = • Excess refrigerant • Improper heat radiation • IPM (Power transistor)
Diagnosis display = F97
Abnormality / Protection control = Outdoor compressor overheating protection
Abnormality Judgement = 4 times occurance within 10 minutes
Emergency operation =
Primary location to verify = • Insufficient refrigerant • Compressor
Diagnosis display = F98
Abnormality / Protection control = Total running current protection
Abnormality Judgement = 3 times occurance within 20 minutes
Emergency operation =
Primary location to verify = • Excess refrigerant • Improper heat radiation
Diagnosis display = F99
Abnormality / Protection control = Outdoor Direct Current (DC) peak detection
Abnormality Judgement = 7 times occurance continuously
Emergency operation =
Primary location to verify = • Outdoor PCB • IPM (Power transistor) • Compressor
S01Room temperature sensor failureRefer to detailed diagnostic
S02Indoor coil sensor failureCheck sensor for continuity
S03Humidity sensor failureReplace indoor board
S04Comp. temperature sensor failureCheck sensor for continuity
S05Outdoor coil sensor failureCheck sensor for continuity
S06Outdoor air sensor failureCheck sensor for continuity
S07Outdoor current sensor failureReplace outdoor board
E01Indoor/outdoor communication failureRefer to detailed diagnostics
E02HIC circuit failure (Compressor/Fan circuit)Refer to detailed diagnostics
E03Outdoor unit OTP rom failureRefer to detailed diagnostics
E04Peak current cut offRefer to detailed diagnostics
E05PAM or Active circuit failureRefer to detailed diagnostics
E06High compressor discharge temperatureRefer to detailed diagnostics
E07Indoor fan operating failureRefer to detailed diagnostics
E084 way valve switching failure (RV)Refer to detailed diagnostics
E09No refrigerant protectionRefer to detailed diagnostics
E10DC compressor drive circuit failureRefer to detailed diagnostics
E11Outdoor fan operating failureRefer to detailed diagnostics
E12Error in outdoor unitRefer to detailed diagnostics
E13Freeze prevention activatedRefer to detailed diagnostics
Panasonic Klima Arıza Kodları Ve Açıklamaları
Panasonic H14 Hata Kodu : İç emme havası sıcaklık sensörü anormallik
Panasonic H15 Hata Kodu : Dış kompresör sıcaklık sensörü anormallik
Panasonic H16 Hata Kodu : Yüksek Akım Trafosu Açık Devre
Panasonic H19 Hata Kodu : Kapalı Fan Motoru Mekanizması Kilitli
Panasonic H23 Hata Kodu : İç Evaparatör Sıcaklık Sensörü Anormallik
Panasonic H24 Hata Kodu : İç Ortam Sıcaklığı Sensörü Anormallik
Panasonic H27 Hata Kodu : Dış Emme Sıcaklık Sensörü Anormallik
Panasonic H28 Hata Kodu : Dış Isı Değiştirici Sıcaklık Sensörü Anormallik
Panasonic H30 Hata Kodu : Dış Tahliye Havası Sıcaklık Sensörü Anormallik
Panasonic H33 Hata Kodu : Besleme Gerilimi Bağlantı Hatası
Panasonic H38 Hata Kodu : Açık Kapalı Uyuşmazlığı Anormallik
Panasonic H50 Hata Kodu : Havalandırma Motoru Anormallik
Panasonic H51 Hata Kodu : Meme Kilit Anormallik
Panasonic H52 Hata Kodu : Limit Kontrol Anormallik
Panasonic H97 Hata Kodu : Açık Fan Motoru Mekanizması Kilitli
Panasonic H98 Hata Kodu : Kapalı Yüksek Basınç Koruma
Panasonic H99 Hata Kodu : Donma Koruma Açık – Yetersiz Gaz Yada Filtre Tıkalı
Panasonic F11 Hata Kodu : 4 Yollu Vana Anormallik
Panasonic F90 Hata Kodu : PFC Kontrol
Panasonic F91 Hata Kodu : Refrigerantion Çevirimi Anormal
Panasonic F93 Hata Kodu : Compresör Çevrimi Anormal
Panasonic F95 Hata Kodu : Serin Yüksek Basınç Koruma
Panasonic F96 Hata Kodu : Güç Transistörü Aşırı Isınma
Panasonic F97 Hata Kodu : Kompresör Aşırı Isı Koruma Açık
Panasonic F98 Hata Kodu : Akım Koruma
S01
Oda sıcaklık sensörü arızası detaylı teşhis bakın
S02
Kapalı bobin sensörü arızası Kontrol sensörü
S03
Nem sensörü arızası kapalı kartını yerine takın
S04
Comp. sürekliliği için sıcaklık sensörü arızası
S05
Açık bobin sensörü arızası
S06
Dış hava sensörü arızası Kontrol sensörü
S07
Dış akım sensörü arızası açık kartını yerine takın
E01
Kapalı / açık iletişim hatası detaylı teşhis bakın
E02
HIC devresi arızası (Kompresör / Fan devre) ayrıntılı teşhis bakın
E03
Dış ünite OTP rom arızası ayrıntılı tanı yöntemlerine bakın
E04
Tepe akımı kesme kapalı ayrıntılı tanı yöntemlerine bakın
E05
PAM veya Active devre arızası ayrıntılı tanı yöntemlerine bakın
E06
yüksek kompresör boşaltma sıcaklığı
E07
İç fan işletim hatası bakın
E08
4 yollu vana arızası anahtarlama
E09
soğutucu koruma detaylı teşhis bakın
E10
DC kompresör tahrik devresi arızası
E11
Açık fan işletim hatası bakın
E12
hatası detaylı teşhis bakın
E13Don önleme Hatası -Deforost
Panasonic Klima Arıza Kod S01
Oda sıcaklık sensörü arızası Ayrıntılı teşhis bölümüne bakın
S02 Kapalı bobin sensörü arızası Sensörü süreklilik açısından kontrol edin
S03 Nem sensörü arızası İç mekan tahtasını değiştirin
S04 Comp. Sıcaklık sensörü arızası Sensörü süreklilik açısından kontrol edin
S05 Dış bobin sensörü arızası Sensörü süreklilik açısından kontrol edin
S06 Dış hava sensörü arızası Sensörü süreklilik açısından kontrol edin
S07 Dış hava akım sensörü arızası Dış hava tahtasını değiştirin
E01 İç / dış mekan iletişim hatası Ayrıntılı teşhis konusuna bakın
E02 HIC devre hatası (Kompresör / Fan devresi) Ayrıntılı teşhis bölümüne bakın
E03 Dış ünite OTP rom arızası Ayrıntılı teşhis konusuna bakın
E04 Pik akım kesilir Ayrıntılı teşhislere bakın
panasonic klima arızaları
E05 PAM veya Aktif devre arızası Ayrıntılı teşhis bölümüne bakın
E06 Yüksek kompresör boşaltma sıcaklığı Ayrıntılı teşhislere bakın
E07 Kapalı fan çalışma hatası Ayrıntılı teşhis bölümüne bakın
E08 4 yönlü valf anahtarlama arızası (RV) Ayrıntılı teşhis bölümüne bakın
E09 Soğutma sıvısı koruması yok Detaylı teşhis başvurun.
E10 DC kompresör tahrik devresi arızası Ayrıntılı teşhis bölümüne bakın
E11 Dış fan çalışma hatası Ayrıntılı teşhis bölümüne bakın
E12 Dış ünite hatası Ayrıntılı teşhis bölümüne bakın
E13 Dondurma önleme aktif Daha detaylı teşhis konusuna bakın
Panasonic Klima Arıza Kodu H00
Herhangi bir anormallik tespit edilmedi – Normal çalışma
H11 İç / Dış mekan anormal iletişim Çalışmaya başlandıktan 1 dakika sonra Sadece iç ünite fan çalışması • Dahili / harici kablo bağlantıları İç / Dış Mekan PCB
H12 Bağlantı yeteneği rütbe anormal
H14 İç hava emişi hava sıcaklık sensörü anormalliği 5 saniye devam edin. Emme havası sıcaklık sensörü (dedektif veya bağlantı kesilmiş)
H15 Dış mekan kompresör sıcaklık sensörü anormalliği 5 saniye Devam – Kompresör sıcaklık sensörü (dedektif veya bağlantı kesikli)
H16 Açık Akım Trafosu açık devre – – • Dış Mekan PCB IPM (Güç transistörü) modülü
H19 Kapalı fan motor mekanizması 7 defa sürekli kilitlendi – • Kapalı PCB Fan motoru
H23 Kapalı eşanjör sıcaklık sensörü anormalliği – O (Sadece soğutma) • Isı eşanjörü sıcaklık sensörü (dedektif veya bağlantı kesikli)
H24 Kapalı eşanjör sıcaklık sensörü 2 anormallik 5 saniye devam edin. – • Isı eşanjörü sıcaklık sensörü (dedektif veya bağlantısız)
H27 Dış hava emiş hava sıcaklık sensörü anormalliği 5 saniye devam edin. O • Dış hava sıcaklık sensörü (dedektif veya bağlantı kesikli)
H28 Dış hava ısı eşanjörü sıcaklık sensörü anormalliği 5 saniye devam edin. O • Dış hava ısı eşanjörü sıcaklık sensörü (dedektif veya bağlantısız)
H30 Dış hava deşarjı hava sıcaklık sensörü anormalliği 5 saniye devam edin. Dış hava sıcaklık sensörü (dedektif veya bağlantısız)
Panasonic Klima Arıza Kodu H33
Kapalı / Açık yanlış bağlantı – – • Kapalı / Açık besleme gerilimi
H38 Kapalı / Açık uyumsuzluk (marka kodu) – – –
H50 Havalandırma motoru anormalliği sürekli 7 kez ortaya çıkıyor – • Kapalı PCB • Havalandırma motoru
H51 Nozul kilidi anormalliği sürekli 2 kez meydana gelir – • Nozul
H52 Limit anahtarı anormalliği – – • Kapalı PCB
H97 Dış fan motor mekanizması 30 dakika içinde 2 kez kilitlendi – • Kapalı PCB • Fan motoru
H98 Kapalı yüksek basınç koruması – – • Hava filtresi kirli • Hava sirkülasyon kısa devresi
H99 İç eşanjör antifriz koruması – – • Yetersiz soğutucu madde Hava filtresi kirli
F11 Soğutma / Isıtma çevrimi değiştirme anormalliği 30 dakika içinde 4 kez oluşabilir – • 4 yönlü valf V-bobin
F90 PFC kontrolü 10 dakika içinde 4 kez meydana gelir – • PFC’deki voltaj
F91 Soğutma sıvısı döngüsü anormalliği 20 dakika içinde 2 kez oluşmuştur – • Soğutucu akışkan yok (3 yönlü vana kapalı)
Panasonic Klima Arıza Kodu F93
Kompresör dönüş hatası 20 dakika içinde 4 kez oluştu – Kompresör
F95 Soğuk yüksek basınç koruması 20 dakika içinde 4 kez oluşabilir – • Dış hava sirkülasyon devresi
F96 IPM (güç transistörü) aşırı ısınmaya karşı koruma 30 dakika içinde 4 kez oluşuyor – Fazla soğutucu akışkan Uygun olmayan ısı yayılımı IPM (Güç transistörü)
F97 Dış mekan kompresör aşırı ısınma koruması 10 dakika içinde 4 kez oluşabilir – • Yetersiz soğutucu madde Kompresör
F98 Toplam çalışma akımı koruması 20 dakika içinde 3 kez oluşur – Fazla soğutucu akışkan Uygun olmayan ısı yayılımı
F99 Dışarıdan Doğru Akım (DC) zirve algılaması sürekli 7 kez meydana gelir – • Dış Mekan PCB IPM (Güç transistörü) Kompresör
Panasonic Klima Arıza Kod Arızaları
Panasonic Klima Servisi
Panasonic klima arızası çözümleri için adresinizde tam destek! Servis Home deneyimli teknisyenleri ve danışmanları ile servis hizmetlerine devam ediyor. Panasonic yetkili servis garantisiyle %100 memnuniyet odaklı çalışıyor.
Panasonic Klima Servisi Çağırmadan Önce Yapmanız Gerekenler
Panasonic klimalar da zamanla ve kullanım koşullarına bağlı olarak arıza gösterebilir. Basit arıza çözümleri ile Panasonic servisine ihtiyacınız olmadan sorunlarınızı çözebilirsiniz.
Panasonic klima arızası için aşağıdaki kontrolleri yaptıktan sonra cihazınızdaki sorun devam ederse, cihaz gürültülü çalışırsa ya da yanık kokusu alırsanız, cihazı hemen durdurun, elektrik sigortasını kapatın ve Panasonic klima servisi çağrı merkezini arayın.
Onarımda ve Bakımda Orijinal Yedek Parça ve Aksesuarlar
Panasonic klima servisi orijinal yedek parça desteğiyle de yanınızda yer alıyor. Klima tamiri ve onarımında kullanılacak olan orijinal yedek parçalar ekonomik fiyatlarla sağlanıyor. Panasonic klima modeline %100 uygun parçaların montajı güvenle yapılıyor. Garantisi geçmiş cihazlarınız için de 1 yıl garantili orijinal yedek parça ve işçilik sunuluyor.
PANASONIC KLİMA ARIZALARIARIZA ÇÖZÜMLERİ
Isıtma soğutma işlemi verimli çalışmıyor.
Isıyı doğru olarak ayarlayın.
Bütün kapıları ve pencereleri kapatın.
Filtreleri temizleyin ve yenisiyle değiştirin.
Hava giriş çıkış ağzındaki tıkanıklığı giderin.
Çalışma esnasında gürültü çıkıyor.
Ünitelerin eğimli kurulup kurulmadıklarını kontrol edin.
Ön paneli düzgün bir şekilde kapatın.
Sorun devam ederse Panasonic klima servisi merkezimizi arayın.
Uzaktan kumanda çalışmıyor. Gösterge bulanık ya da sinyal zayıf.
Pilleri düzgün bir şekilde yerleştirin.
Zayıf pilleri değiştirin.
Sorun devam ederse Panasonic klima onarımı merkezimizi arayın.
Ünite çalışmıyor.
Şalterin atıp atmadığını kontrol edin.
Zaman ayarlayıcının ayarlanıp ayarlanmadığını kontrol edin.
Alıcı önünde tıkanıklık olup olmadığından emin olun.
Ünite uzaktan kumanda sinyali almıyor.
Bazı ışıklar sinyal yayıcıyı etkileyebilir. Panasonic yetkili servisi numaramızı arayın.
İç üniteden sis geliyor.
Soğutma süreci yoğunlaşma etkisi yüzündendir.
Sorun devam ederse Panasonic klima onarımı merkezimizi arayın.